Key Metrics: Lux, UGR and Uniformity
Three metrics define lighting quality for any interior space:
• Lux (lx) — the illuminance measured on the task plane (typically a desk surface at 0.7m height or the floor for circulation). BS EN 12464-1 specifies minimum maintained illuminance for every task type: 500 lux for offices, 300 lux for corridors, 200 lux for stores, 750 lux for detailed inspection areas.
• UGR (Unified Glare Rating) — a measure of discomfort glare from luminaires in the field of view. Lower is better. BS EN 12464-1 specifies maximum UGR limits: ≤ 19 for offices and classrooms, ≤ 22 for industrial, ≤ 25 for corridors. UGR depends on luminaire type, mounting height, room geometry and surface reflectances — it is not a fixed property of the luminaire alone.
• Uniformity (Uo) — the ratio of minimum to average illuminance across the task area. Higher uniformity means more even light distribution. BS EN 12464-1 requires Uo ≥ 0.6 for the task area and Uo ≥ 0.4 for the immediate surrounding area. Poor uniformity creates dark patches and visual discomfort.
Room Index and Utilisation Factor
The room index (RI or K) is a dimensionless number that describes the proportions of a room relative to the luminaire mounting height:
K = (L × W) / (Hm × (L + W))
Where L = room length, W = room width, Hm = mounting height above the working plane.
A large, low room has a high room index (K > 3) — light bounces efficiently between surfaces. A small, tall room has a low room index (K < 1) — much light is absorbed by walls before reaching the working plane.
The utilisation factor (UF) is the proportion of the luminaire's total light output that actually reaches the working plane, after accounting for room geometry, surface reflectances (ceiling, walls, floor) and the luminaire's light distribution. UF tables are provided in photometric data files for each luminaire.
A typical UF for a recessed office luminaire in a medium-sized room with light surfaces is 0.5–0.7, meaning 50–70% of the luminaire's output reaches the desk.
The Lumen Method Calculation
The lumen method is the standard manual calculation for determining the number of luminaires required:
N = (E × A) / (n × Φ × UF × MF)
Where: • N = number of luminaires required • E = required maintained illuminance (lux) • A = area of the room (m²) • n = number of lamps per luminaire (1 for LED) • Φ = luminaire luminous flux (lumens) • UF = utilisation factor • MF = maintenance factor (accounts for light output depreciation and dirt accumulation, typically 0.8 for LED in clean environments)
Example: Office 10m × 8m, 500 lux required, luminaire output 4000 lm, UF 0.6, MF 0.8
N = (500 × 80) / (1 × 4000 × 0.6 × 0.8) = 40,000 / 1,920 = 20.8 → 21 luminaires
The lumen method provides a good starting estimate but does not verify uniformity or UGR. For these, point-by-point computer calculations are essential.
Software Tools for Lighting Design
Professional lighting design uses specialist software that performs point-by-point calculations across a 3D model of the space:
• DIALux — free software widely used in the UK and Europe. Imports IES/LDT photometric files, models complex room geometries, calculates lux grids, uniformity, UGR, and produces professional reports.
• Relux — similar to DIALux with strong energy calculation features and daylight integration.
• AGi32 — used primarily in North America but capable of complex exterior and sports lighting designs.
These tools calculate illuminance at every point on a grid across the working plane, taking into account direct light from luminaires, inter-reflections between surfaces, and furniture obstructions. They produce false-colour renders, iso-contour plots, and tabular results that form the basis of lighting design submissions.
All EOS luminaires are available with IES and LDT photometric data files for immediate use in DIALux and Relux.
Why Professional Lighting Design Matters
A properly calculated lighting design ensures:
• Compliance with BS EN 12464-1 — demonstrating that illuminance, UGR and uniformity meet the standard for every task area
• Energy efficiency — optimising luminaire spacing and output to avoid over-lighting (which wastes energy) or under-lighting (which creates visual discomfort and risks non-compliance)
• Part L compliance — the design provides the LENI data needed for Building Regulations submissions
• BREEAM evidence — Hea 01 credits require documented lighting design calculations demonstrating UGR and illuminance compliance
• Cost optimisation — accurate designs avoid over-specification (too many luminaires) or under-specification (requiring expensive remedial work)
EOS offers a free lighting design service to architects, specifiers and contractors. Our in-house design team produces full DIALux calculations, layout drawings and specification schedules for any project — from a single office to a complete hospital.
Related Pages
More Guides
How to Light an Office
Never has the need for great office lighting been more imperative. This guide co…
How to Light a Living Wall
Living walls — vertical greening typologies where a built structure is intention…
How to Light a Classroom
Getting classroom lighting right has a measurable impact on student performance,…
How to Light an Urban Landscape
Urban landscape lighting shapes how people experience public spaces after dark —…
How to Light a New Build Estate
Lighting new build residential estates involves navigating a unique set of UK re…
How to Light a Warehouse
Warehouse lighting directly affects productivity, safety, pick accuracy and ener…